Phenolic Foam Air Duct Panel
Item No.: WT2-3A
Material: Double side aluminum foil+Phenolic Foam Air Duct
Thickness of aluminum foil: 80um
Total thickness: 20mm
Size: 1.2m(w)x4m(L)
MOQ: 210sheets(1008 square meter)
Item No.: WT2-3B
Material: Aluminum foil+Phenolic Foam Air Duct+steel sheet
Thickness of aluminum foil: 80um
Thickness of Steel: 200um
Total thickness: 20mm
Size: 1.2m(w)x3m(L)
MOQ: 280sheets(1008 square meter)
Item No.: WT2-3C
Material: Double side steel sheet+Phenolic Foam Air Duct
Thickness of Steel: 200um
Total thickness: 20mm
Size: 1.2m(w)x3m(L)
MOQ: 280sheets(1008 square meter)
Phenolic foam air duct panel is widely used in central air-conditioning ducting.
Its of good appearance, beautiful colors, light weight, high strength and easy installation. Its fire-proof, water-proof and of good insulation property. By using this material, the user can save a lot of costs and time.
Its widely used in insulation workshops, cleaning rooms, high class buildings, composite cold storages, containers, etc.
ITEM |
UNIT |
SPECIFICATION |
Density |
kg/m3 |
60-70 |
Double side Aluminum thickness |
mm |
0.08 |
Total thickness |
mm |
20 |
Thermal Conductivity |
w/m. k |
0.02 |
Flexural Strength |
Mpa |
1 |
combustion property |
~ |
Non-combustible Class A |
Water Absorption Rate |
% |
1.9 |
Max Smoke Density |
% |
2 |
Dimension Change Rate |
% |
0.3 |
Compressive Strength |
Mpa |
0.25 |
Service Temperature |
|
-250 to150 |
Standard Size |
mm |
4000*1200*20 |
Technical Data Sheet of Phenolic Foam Panel with Colored Steel |
ITEM |
UNIT |
SPECIFICATION |
Density |
kg/m3 |
60-70 kg/m3 |
Aluminum thickness |
mm |
0.08 |
Steel thickness |
mm |
0.2 |
Total thickness |
mm |
20 |
Dimension |
mm |
4000*1200*20 |
Temperature range |
centigrade |
-180 to 140 |
Thermal conductivity |
w/m. k |
0.020-0.037 |
Firproofing performance |
~ |
Glass 1 (BS 476 part 6& 7) |
Oxygen index |
% |
36-43 |
Grade of smoke density |
~ |
4 SDR |
Water vapor transmission |
g/(m2.24h) |
< 1 |
Compression strength |
pa |
1500 |
Flexural strength |
Mpa |
1 |
Air leakage |
% |
< 2 |
Material water absorption rate |
% |
< 1.5 |
Mechanical loss rate |
~ |
0.01 |
Recycle rate |
% |
60-80 |
life time |
years |
20-30 |
Product Show